Character | Meaning | Typical results | Other info | Return value in quotes or Status without quotes | |
---|---|---|---|---|---|
^A | Model string | SMART-UPS 700 | Spotty support for this query on older models | Not tested | |
^N | Turn on UPS | n/a |
Send twice with > 1.5s delay between chars
Only on 3rd gen SmartUPS and Black Back-UPS Pros |
Not tested | |
^Z | Capability string | (long string) | See "Capabilities" section for more info | Not tested | |
A | Front panel test | Light show + "OK" | Also sounds the beeper for 2 seconds | Works | |
B | Battery voltage | 27.87 |
This obviously varies a lot based on the current charge.
Compare this to the nominal battery voltage |
Works | |
C | Internal temperature | 036.0 | Units are degrees C | Works | |
D | Runtime calibration | !, then $ |
Runs until battery is below 25% (35% for Matrix)
This updates the 'j' values - only works at 100% battery charge Can be aborted with a second "D" |
Not tested | |
E | Automatic selftest intervals | 336 |
Writable variable
Values:
|
Returns only 'OK' | |
F | Line frequency, Hz | 60.00 | If this varies much, have a word with your local electrician | Works ('50.00'Hz here, Europe/Germany) | |
G | Cause of transfer | O |
Writable variable
Values:
|
Not tested | |
I |
Measure-UPS
Alarm enable |
FF | (not yet decoded)(bitmapped table, coming soon) | Returns nothing | |
J |
Measure-UPS
Alarm status |
0F,00 | (not yet decoded)(bitmapped table, coming soon) | Returns nothing | |
K | Shutdown with grace period | OK |
Send twice with > 1.5s delay between chars
Older units may send "*" instead of "OK" Also see grace period |
Not tested | |
L | Input line voltage | 118.3 | Does not necessarily read 000.0 on line failure | Works | |
M | Maximum line voltage | 118.9 | This is the max voltage since the last time this query was run | Works | |
N | Minimum line voltage | 118.9 | Like the one above, this one also resets itself on every query | Works | |
O | Output voltage | 118.3 | Also see on battery output voltage | Works | |
P | Power load % | 023.5 | Relative to the capacity of the UPS | Works | |
Q | Status flags | 08 | See status flags section for more info | Works (Only '08' and '10' tested) | |
R | Turn dumb | BYE |
Only on 3rd gen Smart-UPS, Smart-UPS v/s, Back-UPS Pro
UPS must receive command to enter smart mode continue communications after sending this | Returns nothing | |
S | Soft shutdown | OK |
Command executes after grace period
UPS goes online when power returns Only works when on battery |
Works (just tested with the default value, nothing has been written by me) | |
U | Simulate power failure | !, then $ | See async notifier section for info on ! and $ | Works (Received 'OK' only) | |
V | Firmware revision | GWD | Can be used to determine abilities of hardware | '6FI' | |
W | Self test | OK |
Tests battery, like pushing the test button on the front panel
Also see test results entry |
Works (Received Nothing) | |
X | Self-test results | OK |
Values:
|
Works Only 'OK' tested) | |
Y | Enter smart mode | SM |
This must be sent before anything else on this page will work.
Also see turn dumb command to exit smart mode |
Works | |
Z | Shutdown immediately | n/a |
Send twice with > 1.5s delay between chars
UPS switches the load off immediately (no grace period) |
Works | |
a | Protocol info | (long string) |
Returns three main sections:
|
Works 'D1' (no long string) | |
b | Firmware revision | 50.9.D |
Decoding above info:
|
Works? 'CF' | |
c | UPS local id | UPS_IDEN |
Writable variable
Up to 8 letter identifier for keeping track of your hardware |
Works? 'D1' | |
e | Return threshold | 00 |
Writable variable
Minimum battery charge % to return from shutdown after power returns Values:
This prevents excessive cycling during multiple power failures |
Not tested | |
g | Nominal battery voltage | 024 |
The battery voltage that's expected to be present in the UPS normally
Compare to the actual voltage reading |
Nothing received | |
f | Battery level | 099.0 |
Percentage
It's much easier to use this rather than doing math on the current battery voltage and the nominal battery voltage |
Nothing received | |
h |
Measure-UPS
Ambient humidity |
042.4 |
Percentage
Only works on models with the Measure-UPS SmartSlot card |
Nothing received (I assume wrong UPS) | |
i |
Measure-UPS
Dry contacts |
00 |
Bitmapped hex variable
Component values:
| Nothing received | |
j | Estimated runtime | 0327: |
Minutes
Must be calibrated to be effective |
Nothing Received | |
k | Alarm delay | 0 |
Writable variable
Values:
Does not affect low battery warning |
Not tested | |
l | Low transfer voltage | 103 |
Writable variable
See capabilities to get values for a UPS UPS goes on battery after voltage drops below this point |
Not tested | |
m | Manufacturing date | 11/29/96 | Format may vary by country (MM/DD/YY vs DD/MM/YY) | Nothing received | |
n | Serial number | WS9643050926 | Unique for each UPS | Nothing Received | |
o | On-battery voltage | 115 | May be a writable variable on 220/230/240 VAC units | Nothing received | |
p | Shutdown grace delay | 020 |
Writable variable - seconds
See capabilities to read values Sets the delay before soft shutdown completes |
Not tested | |
q | Low battery warning | 02 |
Writable variable - minutes
See capabilities to read values The UPS will report a low battery this many minutes before it runs out of power |
Not tested | |
r | Wakeup delay | 000 |
Writable variable - seconds
See capabilities to read values The UPS will wait this many seconds after reaching the minimum charge before returning online |
Not tested | |
s | Sensitivity | H |
Writable variable
See capabilities to read values Meaning of values:
|
Not tested | |
u | Upper transfer voltage | 132 |
Writable variable
See capabilities to read values UPS goes on battery after voltage rises above this poiont |
Not tested | |
v |
Measure-UPS
Firmware | 4Kx | Firmware information for Measure-UPS board | Not tested | |
t |
Measure-UPS
Ambient temperature | 80.5 |
Degrees C
Only works on models with the Measure-UPS SmartSlot card |
Nothing received (I assume wrong UPS) | |
x | Last battery change | 11/29/96 |
Writable variable
This holds whatever the user sets in it, much like the UPS local id variable |
Not tested | |
y | Copyright notice | (C) APCC | Only works if firmware letter is later than O | Nothing received | |
z | Reset to factory settings | CLEAR |
Resets most variables to initial factory values except
identity or battery change date
Not on SmartUPS v/s or BackUPS Pro |
Nothing received | |
- | Capability cycle | (various) |
Cycle through possible capability values
UPS sends | afterward to confirm change to PROM |
Not tested | |
@nnn | Shutdown and return | OK |
UPS shuts down after grace period with delayed wakeup
after nnn tenths of an hour plus any wakeup delay time
Some older models send * instead of OK |
Not tested | |
0x7f | Abort shutdown | OK |
Abort shutdown - use to abort @,
S, K
Also known as the delete key in some places |
Not tested | |
~ | Register #1 | n/a | See register 1 table | Not tested | |
' | Register #2 | n/a | See register 2 table | Not tested | |
7 | Dip switch positions | n/a |
See dip switch table
Only makes sense on models which actually have dip switches |
Not tested | |
8 | Register #3 | n/a | See register 3 table | Not tested | |
9 | Line quality | FF |
Values
|
Works | |
> | Battery packs | n/a |
SmartCell models: returns number of connected packs
Non-SmartCell models: returns number set by user (use + and -) |
Not tested | |
[ |
Measure-UPS
Upper temp limit |
NO,NO | Degrees C
Writable variable Values: 55,50,45,...,05 for both Use - to enumerate through left side, + to enumerate through right side |
Not tested | |
] |
Measure-UPS
Lower temp limit |
NO,NO | Degrees C
Writeable variable See 'lower temp limit' above |
Not tested | |
{ |
Measure-UPS
Upper humidity limit |
NO,NO | %
Writable variable Values: 90,80,70,...,10 for both Use - and + to change values |
Not tested | |
} |
Measure-UPS
Lower humidity limit |
NO,NO | %
Writable variable Values: 90,80,70,...,10 for both Use - and + to change values |
Not tested | |
Matrix-UPS and Symmetra commands | |||||
^ | Run in bypass mode | n/a |
If online, "BYP" response is received as bypass mode starts
If already in bypass, "INV" is received and UPS goes online If UPS can't transfer, "ERR" received |
||
< | Number of bad battery packs | 000 | Returns count of bad packs connected to the UPS | ||
/ | Load current | n/a | True RMS load current drawn by UPS | ||
\ | Apparent load power | n/a | Output load as percentage of full rated load | ||
^V | Output voltage selection | n/a |
Writable variable
Values:
|
||
^L | Front panel language | n/a |
Writable variable
Values:
Also 1, 2, 3, 4 - unknown |
||
w | Run time conservation | n/a |
Writable variable
Values:
|
Bit | Switch | Option when bit=1 |
---|---|---|
0 | 4 | Low battery alarm changed from 2 to 5 mins. Autostartup disabled on SU370ci and 400 |
1 | 3 | Audible alarm delayed 30 seconds |
2 | 2 | Output transfer set to 115 VAC (from 120 VAC) or to 240 VAC (from 230 VAC) |
3 | 1 | UPS desensitized - input voltage range expanded |
4-7 | - | Unused at this time |
Bit | Meaning |
---|---|
0 | 1 = runtime calibration occurring
Not reported by Smart UPS v/s and BackUPS Pro |
1 | 1 = SmartTrim
Not reported by 1st and 2nd generation SmartUPS models |
2 | 1 = SmartBoost |
3 | 1 = on line |
4 | 1 = on battery |
5 | 1 = overloaded output |
6 | 1 = battery low |
7 | 1 = replace battery |
Character | Description |
---|---|
! | Line Fail - sent when the UPS goes on-battery, repeated every 30 seconds until low battery condition reached. Sometimes occurs more than once in the first 30 seconds. |
$ | Return from line fail - UPS back on line power, only sent if a ! has been sent. |
% | Low battery - Sent to indicate low battery, but not on SmartUPS v/s or BackUPS Pro models |
+ | Return from low battery - Sent when the battery has been recharged to some level only if a % has been sent previously |
? | Abnormal condition - sent for conditions such as "shutdown due to overload" or "shutdown due to low battery capacity". Also occurs within 10 minutes of turnon. |
= | Return from abnormal condition - Sent when the UPS returns from an abnormal condition where ? was sent, but not a turn-on. Not implemented on SmartUPS v/s or BackUPS Pro models. |
* | About to turn off - Sent when the UPS is about to switch off the load. No commands are processed after this character is sent. Not implemented on SmartUPS v/s, BackUPS Pro, or 3rd generation SmartUPS models. |
# | Replace battery - Sent when the UPS detects that the battery needs to be replaced. Sent every 5 hours until a new battery test is run or the UPS is shut off. Not implemented on SmartUPS v/s or BackUPS Pro models. |
& | Check alarm register for fault (Measure-UPS) - sent to signal that temp or humidity out of set limits. Also sent when one of the contact closures changes states. Sent every 2 minutes, stops when the alarm conditions are reset. Only sent for alarms enabled with I. Cause of alarm may be determined with J. Not on SmartUPS v/s or BackUPS Pro. |
| | Variable change in EEPROM - Sent whenever any EEPROM variable is changed. Only supported on Matrix UPS and 3rd generation SmartUPS models. |
Bit | Meaning |
---|---|
0 | In wakeup mode (typically lasts < 2s) |
1 | In bypass mode due to internal fault - see register 2 or 3 |
2 | Going to bypass mode due to command |
3 | In bypass mode due to command |
4 | Returning from bypass mode |
5 | In bypass mode due to manual bypass control |
6 | Ready to power load on user command |
7 | Ready to power load on user command or return of line power |
Bit | Meaning |
---|---|
0 | Fan failure in electronics, UPS in bypass |
1 | Fan failure in isolation unit |
2 | Bypass supply failure |
3 | Output voltage select failure, UPS in bypass |
4 | DC imbalance, UPS in bypass |
5 | Command sent to stop bypass with no battery connected - UPS still in bypass |
6 | Relay fault in SmartTrim or SmartBoost |
7 | Bad output voltage |
Bit | Meaning |
---|---|
0 | Output unpowered due to shutdown by low battery |
1 | Unable to transfer to battery due to overload |
2 | Main relay malfunction - UPS turned off |
3 | In sleep mode from @ (maybe others) |
4 | In shutdown mode from S |
5 | Battery charger failure |
6 | Bypass relay malfunction |
7 | Normal operating temperature exceeded |
#uD43132135138129uM43229234239224uA43110112114108 ....
It looks bizarre and ugly, but is easily parsed. The # is some kind of marker/ident character. Skip it. The rest fits this form:
Matrix-UPS models have ## between each grouping for some reason.